SD20/30R series, T2

Max. Continuous Operating Voltage (Uc): L-N: 385 VAC, N-PE: 255 VAC

Nominal Discharge Current  (In(8 / 20 μs): 20 / 30 kA

Max. Discharge Current (Imax) (8 / 20 μs): 40 / 60 kA

Protection Mode: 1+1 (L–N, N-PE)

Manufacturer

Xiamen SET Electronics Co., Ltd.

Features

● For Single-Phase System

● MOV Module Tripping Ability: 800 V, 100 A

● High Environmental Adaptability

● With Remote Signaling and Failure Indicator

● RoHS & REACH Compliant

Applications

● AC / DC Power System

● New Energy

● Residential Building

● Telecommunications

● Internet Data Center (IDC)

● Distribution System

Technology Applications Markets Applications

Design Standards & Agency Approvals

ABSOLUTELY ASSURED USE WITH GLOBALIZATION CERTICATION


SD20R series

UL (America):

Standards: UL 1449

File NO.: E322662

UL_SPD_SD20R_SETsafe & SETfuse.pdf

 

cUL (Canada):

Standards: CSA C22.2 No. 269  

File NO.: E322662

cUL_SPD_SETsafe & SETfuse.pdf

 

TUV (Germany):

Standards: EN 61643-11

File NO.: R50441567

TUV_SPD_SD20R_SETsafe & SETfuse.pdf


Quality Assurance

For product quality, our goal is to be industry-leading. We ensure that the quality of the product meets the expected goals from the following process.

 

Quality Policy.

Qualified Supplier of Raw Materials.

IQC (AQL, Dimension, Function, Visual Inspection, RoHS & REACH Test).

Process, Online Inspection and Testing (Function 100% Test).

IPQC (AQL, Dimension, Function, Visual Inspection).

FQC (AQL, Dimension, Function, Visual Inspection, RoHS & REACH Test).

Reliability Test (AQL).

OQC (Packaging, Labeling, Quantity Inspection).

Agency (Safety Certificate) Annual, Quarterly Audits.

Quality Management System (TUV Approved and issued certificate).

Brand

SETsafe | SETfuse


Brand Story.png

Tradename

SETsafe

Overview

Din-rail Surge Protective Device

Surge protective devices (SPDs) are designed to meet requirements for UL 1449 Forth Edition and IEC/EN 61643-11. They are DIN-rail mountable featuring a fail-safe protection, visual indicator and remote signal contact. It has a good environmental adaptability and meets the requirements of high reliability in important field.

SD20 30R系列 T2 1+1-1.png

SD20/30R series, T2